Available Fault Current Calculator ๐ ๐
Get from utility: Fault MVA or Short-circuit current at transformer primary .
I_fault = (Transformer FLA) / (%Z/100) Where FLA = (kVA ร 1000) / (V_secondary ร โ3 for 3โphase) available fault current calculator
For a secondary fault:
Cable impedance reduces AFC to โ 9.2 kA at the panelboard. Get from utility: Fault MVA or Short-circuit current
Long cables reduce AFC. Subtract voltage drop impedance from available current. โ ๏ธ Manual calculations are errorโprone for complex systems. Use a dedicated calculator or software (e.g., EasyPower, SKM, ETAP, or web tools like Copper Bussmann FC2). Example Scenario Transformer: 500 kVA, 480V secondary, 5.75% Z FLA secondary = 500,000 / (480 ร 1.732) โ 601 A I_fault (transformer terminals) = 601 / (0.0575) โ 10,452 A (10.45 kA) 5.75% Z FLA secondary = 500